Language

Go Back
Home > Product > Industrial Network > IO-Link Master > EtherCAT & IO-Link master

EtherCAT & IO-Link master

Support EtherCAT protocol, IO-Link Master, 4 ports, Class B, 006BA1
Support EtherCAT protocol, IO-Link Master, 4 ports, Class B, 006BA1
Support EtherCAT protocol, IO-Link Master, 4 ports, Class B, 006BA1
Support EtherCAT protocol, IO-Link Master, 4 ports, Class B, 006BA1

Support EtherCAT protocol, IO-Link Master, 4 ports, Class B, 006BA1

Ordering code:006BA1 Part number :FNI ECT-502-105-S

IO-Link M12集线器 16×DI PNP(图1)

> Can connect 4 IO-Link protocol devices

> Integrated EtherCAT fieldbus interface

> Protection class: IP 67 (when properly connected)

>Wide operating temperature range: -25...+70℃

> Shell material: Nickel-plated Gd-Zn alloy

Collect
Function Parameter Resource Download Related accessories


Technical data


Network protocol

EtherCAT

Rated working voltage UB

18...30 V DC

Module current consumption

≤ 130 mA

Auxiliary input/output power status

US/UA

Module status indicator

Yes

Network status indicator

Yes

Port status indicator

Red,Yellow

Connection: Fieldbus

M8,4 Pin,Female

Connection: AUX power

M8,4 Pin,Male/Female

Connection: I/O port

M12,A-coded,4 Pin,Female

Number of I/O ports

4

Input quantity

Up to 4 PNP inputs

Output quantity

-

Input/output configurable

Yes

Maximum load current, sensor/channel

200 mA

Maximum output load current

2 A

Port status indicator (signal status)

Yellow LED indicator light

Port diagnostic light (overload)

Red LED indicator light

Total current U actuator

≤ 4 A

Total current U sensor

≤ 4 A

Degree of protection as per IEC 60529

IP67(When connected correctly)

Operating temperature

-25...+70℃

Storage temperature

-25...+85℃

Fastener

2 pcs mounting hole

Dimensions (length × width × height)

145×32×33 mm

Shell materialNickel plated Gd-Zn alloy

Weight

-



IO-Link data


IO-Link Master

4×IO-Link

IO-Link version

1.1

Port level 

Class B

IO-Link main port

0...3 Ports for input/output devices

Working mode (3 wire)

SIO、COM 1、COM 2、COM 3

Indicator light communication

Green LED indicator light

Indicator light error

Red LED indicator light

IO-Link Maximum load current of the device

2 A