> Can connect 8 IO-Link protocol devices
> Integrated EtherCAT fieldbus interface
> Protection class: IP 67 (when properly connected)
>Wide operating temperature range: -25...+70℃
> Shell material: Nickel-plated Gd-Zn alloy
Technical data
Network protocol | EtherCAT |
Rated working voltage UB | 18...30 V DC |
Module current consumption | ≤ 130 mA |
Auxiliary input/output power status | US/UA |
Module status indicator | Yes |
Network status indicator | Yes |
Port status indicator | Red,Yellow |
Connection: Fieldbus | M12,D-coded,Female |
Connection: AUX power | M12,L-coded,Male/Female |
Connection: I/O port | M12,A-coded,Female |
Number of I/O ports | 8 |
Input quantity | Up to 16 PNP inputs |
Output quantity | Up to 8 PNP output |
Input/output configurable | Yes |
Maximum load current, sensor/channel | 200 mA |
Maximum output load curren | 2 A |
Port status indicator (signal status) | Yellow LED indicator light |
Port diagnostic light (overload) | Red LED indicator light |
Total current U actuator | ≤ 16 A |
Total current U sensor | ≤ 16 A |
Degree of protection as per IEC 60529 | IP67(When connected correctly) |
Operating temperature | -25...+70℃ |
Storage temperature | -25...+85℃ |
Fastener | 2 pcs mounting hole |
Dimensions (length × width × height) | 223×65×25.8 mm |
Shell material | Nickel plated Gd-Zn alloy |
Weight | - |
IO-Link data
IO-Link Master | 8×IO-Link |
IO-Link version | 1.1 |
Port level | Class A |
IO-Link main port | 0...3 Ports for input/output devices;4...7 Ports for input devices |
Working mode (3 wire) | SIO、COM 1、COM 2、COM 3 |
Indicator light communication | Green LED indicator light |
Indicator light error | Red LED indicator light |
IO-Link Maximum load current of the device | 2 A |
Ordering code:006B11
Ordering code:006B31
Ordering code:006B51
Ordering code:006BA1