>Can connect 8 IO-Link protocol devices
>Integrated Profinet, Ethernet/IP, CC-Link IEF Basic fieldbus interface
>Protection level: IP 67 (when correctly connected)
>Wide working temperature range: -25...+70 ℃
>Shell material: Nickel plated Gd-Zn alloy
Technical data
Network protocol | Profinet、Ethernet/IP、CC-Link IEF Basic |
Rated working voltage UB | 18...30 V DC |
Module current consumption | ≤ 130 mA |
Auxiliary input/output power status | US/UA |
Module status indicator | Yes |
Network status light | Yes |
Port status indicator | Red,Yellow |
Connection: Fieldbus | M12,D-coded,Female |
Connection: AUX power | M12,L-coded,Male/Female |
Connection: I/O port | M12,A-coded,Female |
Number of I/O ports | 8 |
Input quantity | Up to 16 PNP input |
Output quantity | Up to 16 PNP output |
Input/output copnfigurable | Yes |
Maximum load current,sensor/channel | 200 mA |
Maximum output load current | 2 A |
Port status indicator (signal status) | Yellow LED indication light |
Port diagnosis light(overload) | Red LED indication light |
Total current U actuator | ≤ 16 A |
Total current Usensor | ≤ 16 A |
Degree of protection as per IEC 60529 | IP67(When connected correctly) |
Operating temperature | -25...+70℃ |
Storage temperature | -25...+85℃ |
Fastener | 2 pcs mounting hole |
Dimensions (length × width × height) | 223×65×25.8 mm |
Shell material | Nickel plated Gd-Zn alloy |
Weight |
IO-Link data
IO-Link Master | 8×IO-Link |
IO-Link version | 1.1 |
Port level | Class A |
IO-Link main port | 0...7 Ports for input/output devices |
Working mode (3 wires) | SIO、COM 1、COM 2、COM 3 |
Indicator light communication | Green LED Indication light |
Indicator light error | Red LED Indication light |
IO-Link Maximum load current of the device | 2 A |